Heat transfer enhancement and performance of compact heat exchangers have been extensively studied in the past century for the purpose of promoting energy efficiency. Microfin tubes in single/two/multiple-phase flow heat… Click to show full abstract
Heat transfer enhancement and performance of compact heat exchangers have been extensively studied in the past century for the purpose of promoting energy efficiency. Microfin tubes in single/two/multiple-phase flow heat exchangers into which twisted tape swirl generators are installed can promote heat transfer with a moderate pressure loss penalty. This article reports on the enhanced heat transfer of silver–water nanofluids in a microfin tube into which loose-fit twisted tapes are installed in a counter-flow arrangement. The experiments were carried out using nanofluids with various silver concentrations (0.007–0.03 vol%), loose-fit twisted tapes with clearance ratios ( c / D ) of 0.0 (tight-fit), 0.05, 0.075 and 0.1, for a twist ratio, y / W , of 2.0. The results indicate that the heat transfer rate (Nu) and pressure drop ( f ) increase with a decrease in clearance ratio ( c / D ) and increase in silver (Ag) nanoparticle concentration. Additionally, the thermal performance factor tends to increase with the decrease in Reynolds numbers.
               