Abstract The current work study the heat dissipation characteristics and airflow distribution in a power cabin. By simplifying the cable structure, a 1:5 reduced-scale model was constructed based on the… Click to show full abstract
Abstract The current work study the heat dissipation characteristics and airflow distribution in a power cabin. By simplifying the cable structure, a 1:5 reduced-scale model was constructed based on the Archimedes number. Computational fluid dynamics (CFD) simulations were applied to the prototype power cabin. The 3D steady-state Reynolds average Navier-Stokes (RANS) equation is used to solve the ventilation flow, where the turbulence model is realizable k–e. The CFD simulation of the prototype has been verified by the reduced-scale model. On this basis, several conclusions were drawn. The airflow distribution in the power cabin and cable arrangement cause a difference in the temperature distribution between the cables. The strong turbulence at the air inlet causes a significant temperature drop. The mechanical fan can effectively cool the cable to a certain extent, but cable temperature control should take into account the effects of ampacity and ventilation, as well as cable location.
               