Abstract This paper studies the effect of the air damper placed downstream of an averaging Pitot tube (APT) on the flow measurement in air distribution systems. Experiments are conducted to… Click to show full abstract
Abstract This paper studies the effect of the air damper placed downstream of an averaging Pitot tube (APT) on the flow measurement in air distribution systems. Experiments are conducted to obtain the characteristic curve of the APT under different damper positions. The analysis of variance (ANOVA) is applied and the results reveals a statistically significant correlation between them. A mathematical model for the pressure coefficient with respect to the damper opening angle is proposed to compensate the systematic error caused by the damper. The model is validated under various Reynolds numbers (Re) varying from 6.38 × 103 to 19.1 × 103 with RMSE
               