Abstract Lightning transient effects on a hybrid 4.1 MW PV–wind system were investigated in this work by using PSCAD/EMTDC software. A simulation was performed with real lightning current waveforms, namely, negative… Click to show full abstract
Abstract Lightning transient effects on a hybrid 4.1 MW PV–wind system were investigated in this work by using PSCAD/EMTDC software. A simulation was performed with real lightning current waveforms, namely, negative first stroke and positive stroke, with and without a lightning protection system. Surge protective devices were also designed based on European Commission for Electrotechnical Standardization (CENELEC) standards. Analyses were performed to determine appropriate ratings for the threat level and specifications of the equipment/components of the hybrid system that can suppress lightning transients to an acceptable voltage level.
               