Abstract In this study, the influence of various air inlet angles on the heat transfer and flow friction characteristics of a 2-row plain finned oval tube heat exchanger is analyzed by experimental and numerical methods. The experimental results show that an air inlet angle 45° provides the best heat transfer performance, and an air inlet angle 90° provides the smallest pressure drop, while an air inlet angle 30° provides the worst heat transfer performance associated with the largest pressure drop. The 3-D numerical simulation results indicate that with the decrease of the air inlet angle, the uniformity of the air velocity distribution in the z-direction of the heat exchanger becomes worse. The heat transfer characteristics at different air inlet angles are analyzed from the prospective of the field synergy principle and the effect of the air velocity distribution uniformity. The overall heat transfer performance is also evaluated by the JF factor under the same air mass flow rate. The results show that the air inlet angle 45° offers the best overall heat transfer performance, next is the air inlet angle 60°, while the air inlet angle 30° has the worst overall heat transfer performance.
               