Abstract In this study, the performance of a counter flow dew point evaporative cooling system has been examined, numerically and experimentally. A one-dimensional (1D) model of the heat and mass… Click to show full abstract
Abstract In this study, the performance of a counter flow dew point evaporative cooling system has been examined, numerically and experimentally. A one-dimensional (1D) model of the heat and mass transfer in the cooling system is presented. In order to assess the 1D model, a detailed three-dimensional (3D) model is developed. Experimental results showed that the wet-bulb effectiveness of the cooling system could reach values as high as 125%. The predicted variations of air temperature along the channels of the cooling system by both models are in fair agreement. On average, the 1D model predicts lower outlet temperatures by about 1.86% relative to the 3D model. While the computational time of the 3D model is about three orders of magnitude higher than the 1D model. The predicted outlet temperature of the cooling system by the 1D and 3D models match the experimental results within 10% and 8.5%, respectively.
               
Click one of the above tabs to view related content.