Arc duration and erosion characteristics of cables are closely related to electrical fire hazards. In this study, the arc duration and arc erosion characteristics of copper and aluminum core cables… Click to show full abstract
Arc duration and erosion characteristics of cables are closely related to electrical fire hazards. In this study, the arc duration and arc erosion characteristics of copper and aluminum core cables were explored. The main erosion modes of copper core cable with mica insulation (HC0) and aluminum core cable with PI insulation (HA0) were determined. Results show that several large molten droplets with diameters of 5±0.5mm would drip down from the molten pool on the cable end during arcing of HC0, but the molten droplets are adhered to the molten pool and do not drip down during arcing of HA0. We concluded that the differences in melting energy and oxide film between copper and aluminum are the main reasons for this phenomenon. Besides, the molten pool can be formed on the cable end as the insulation is heatproof, which plays a vital role in prolonging the arc duration of cables. The arc duration of cables with heatproof insulation is longer than those with common insulation. This means that the cables with heatproof insulation have higher fire hazards from the perspective of arc duration. To further understand the influence of molten pools on arc duration, an arc duration model was developed based on energy balance, which is beneficial in determining the arc duration of cables with heatproof insulation in electrical fire accident investigation.
               