LAUSR.org creates dashboard-style pages of related content for over 1.5 million academic articles. Sign Up to like articles & get recommendations!

Monitoring Electrical and Thermal Characteristics of HTS Cable Systems via Time–Frequency Domain Reflectometry

Photo from wikipedia

A high-temperature superconducting (HTS) cable system with the 22.9 kV, 50 MVA, and 410 m length is installed and operated at 154 kV Icheon substation of Korea Electric Power Corporation… Click to show full abstract

A high-temperature superconducting (HTS) cable system with the 22.9 kV, 50 MVA, and 410 m length is installed and operated at 154 kV Icheon substation of Korea Electric Power Corporation (KEPCO). Unfortunately, it is a difficult task to diagnose and monitor electrical and thermal characteristics of the HTS cable system in a real-time manner. In order to protect operational failures of grid-connected HTS cable systems, this paper proposes time–frequency domain reflectometry (TFDR) and analysis techniques, i.e., time-frequency cross correlation and instantaneous frequency estimation. To verify the performance of the proposed method, the temperature is changed via the cryogenic refrigeration system and the status of the grid-connected HTS cable is monitored via TFDR in a real-time manner.

Keywords: electrical thermal; hts cable; cable; time frequency

Journal Title: IEEE Transactions on Applied Superconductivity
Year Published: 2017

Link to full text (if available)


Share on Social Media:                               Sign Up to like & get
recommendations!

Related content

More Information              News              Social Media              Video              Recommended



                Click one of the above tabs to view related content.