LAUSR.org creates dashboard-style pages of related content for over 1.5 million academic articles.
Sign Up to like articles & get recommendations!
Shaving Data Center Power Demand Peaks Through Energy Storage and Workload Shifting Control
This paper proposes efficient strategies that shave Data Centers (DCs)’ monthly peak power demand with the aim of reducing the DCs’ monthly expenses. Specifically, the proposed strategies allow to decide:… Click to show full abstract
This paper proposes efficient strategies that shave Data Centers (DCs)’ monthly peak power demand with the aim of reducing the DCs’ monthly expenses. Specifically, the proposed strategies allow to decide: $i)$i) when and how much of the DC's workload should be delayed given that the workload is made up of multiple classes where each class has a certain delay tolerance and delay cost, and $ii)$ii) when and how much energy should be charged/discharged into DCs’ batteries. We first consider the case where the DC's power demands throughout the whole billing cycle are known and present an optimal peak shaving control strategy for it. We then relax this assumption and propose an efficient control strategy for the case when (accurate/noisy) predictions of the DC's power demands are only known for short durations in the future. Several comparative studies based on real traces from a Google DC are conducted in order to validate the proposed techniques.
Share on Social Media:
  
        
        
        
Sign Up to like & get recommendations! 1
Related content
More Information
            
News
            
Social Media
            
Video
            
Recommended
               