LAUSR.org creates dashboard-style pages of related content for over 1.5 million academic articles. Sign Up to like articles & get recommendations!

Effect of cumulative moisture content on degradation of transformer paper insulation

Photo from wikipedia

Nowadays, reliability of power system is of great importance. Therefore, the condition of transformers as the expensive and critical components of a power system should be monitored and assessed. The… Click to show full abstract

Nowadays, reliability of power system is of great importance. Therefore, the condition of transformers as the expensive and critical components of a power system should be monitored and assessed. The dominant factor that causes limitation in transformers lifetime is the paper insulation. This paper aims to investigate the conspicuous influence of moisture content, especially in low oxygen and temperature on lifetime estimation under constant conditions, based on the results of previous experiments. Degree of polymerization (DP) is employed to quantify the effects of detrimental parameters with respect to their time-varying nature. This paper proposes a novel lifetime estimation-approach considering a yearly moisture growth for transformers. The results indicate different trend of DP profiles, which lead to an accurate lifetime estimation in comparison with DP obtained through ideal conditions. Furthermore, oscillations in the hot-spot temperature of transformers are demonstrated to have a negative effect on the lifetime.

Keywords: insulation; moisture content; paper insulation; paper

Journal Title: IEEE Transactions on Dielectrics and Electrical Insulation
Year Published: 2017

Link to full text (if available)


Share on Social Media:                               Sign Up to like & get
recommendations!

Related content

More Information              News              Social Media              Video              Recommended



                Click one of the above tabs to view related content.