Partial discharge (PD) in gas insulated switchgear (GIS) has been studied extensively under AC voltage or transient voltage applied alone. However, the transient voltage in an actual system is superimposed… Click to show full abstract
Partial discharge (PD) in gas insulated switchgear (GIS) has been studied extensively under AC voltage or transient voltage applied alone. However, the transient voltage in an actual system is superimposed on the AC operating voltage, which has rarely been studied. In this paper, the effect of AC and switching impulse superimposed voltage on PD characteristics was studied in SF6 gas. A test platform of generating superimposed voltage with controllable phase was used to study free particle and floating potential defect models. When the AC voltage was 90 and 110% of PD inception voltage (PDIV), the standard switching impulse with amplitude of about twice the PDIV was superimposed on different phases of the AC voltage. When the AC voltage is below the PDIV, results show that PDs of free particle defect model can be initiated when switching impulse is superimposed on 45 and 90° of AC. The PDs in the subsequent cycles of AC reignited into a self-sustaining discharge. For the floating potential defect, PDs have a marked difference duration, which is initiated by switching impulse in different phase. However, there is no change in PDs in each model when the AC voltage is above the PDIV.
               