LAUSR.org creates dashboard-style pages of related content for over 1.5 million academic articles. Sign Up to like articles & get recommendations!

Virtual Flux Direct Power Control for PWM Rectifiers Based on an Adaptive Sliding Mode Observer

Photo by karsten_wuerth from unsplash

In the traditional virtual flux estimation for a three-phase pulsewidth modulation rectifier, the integration element causes problems for the initial value and dc bias, and the unstable grid voltage induces… Click to show full abstract

In the traditional virtual flux estimation for a three-phase pulsewidth modulation rectifier, the integration element causes problems for the initial value and dc bias, and the unstable grid voltage induces a nonconstant flux amplitude. To address these issues, an improved direct power control scheme based on an adaptive sliding mode observer is proposed in this work. The observer employs a sigmoid function as switch function to estimate the grid-side source voltage. Meanwhile, an adaptive compensator instead of pure integral element is also designed to dynamically adjust compensation. The stability of this observer is proved by the Lyapunov function; moreover, simulations and experimental results indicate that this new virtual flux observer substantially improves the observation accuracy based on voltage sensorless control. The application of this strategy successfully suppresses the fluctuation of the dynamic voltage response in the dc bus, eliminating high-frequency noise from the grid side, while simultaneously boosting the power quality.

Keywords: power control; flux; direct power; virtual flux

Journal Title: IEEE Transactions on Industry Applications
Year Published: 2018

Link to full text (if available)


Share on Social Media:                               Sign Up to like & get
recommendations!

Related content

More Information              News              Social Media              Video              Recommended



                Click one of the above tabs to view related content.