The influence of conductor surface conditions of new and aged conductors on ground-level resultant electric field and ion current density is analyzed in this paper. The surface roughness and morphology… Click to show full abstract
The influence of conductor surface conditions of new and aged conductors on ground-level resultant electric field and ion current density is analyzed in this paper. The surface roughness and morphology of conductors are measured and analyzed by 3-D phase shift Micro-Xam (MicroXAM-3D) and scanning electron microscopy. Calculations are made using the upstream finite-element-finite difference method for the corona cage model to obtain the influence of surface conditions on the ion-flow field, consequently, changing the resulting electric field and ion current density. An indoor corona cage platform is build up to check the impact of surface conditions on the ground-level resultant electric field and ion current density in the laboratory. Considering the aging characteristics of the conductor surface, a typical ${\pm}$800 kV ultra-high voltage direct current transmission line is analyzed. The calculated results show that compared with the new conductor, the electric field and ion current density of the long-term operation conductors increase very significantly.
               
Click one of the above tabs to view related content.