Phase imbalance in the U.K. and European low-voltage (415 V, LV) distribution networks causes additional energy losses. A key barrier against understanding the imbalance-induced energy losses is the absence of high-resolution… Click to show full abstract
Phase imbalance in the U.K. and European low-voltage (415 V, LV) distribution networks causes additional energy losses. A key barrier against understanding the imbalance-induced energy losses is the absence of high-resolution time-series data for LV networks. It remains a challenge to estimate imbalance-induced energy losses in LV networks that only have the yearly average currents of the three phases. To address this insufficient data challenge, this paper proposes a new customized statistical approach, named as the clustering, classification, and range estimation (CCRE) approach. It finds a match between the network with only the yearly average phase currents (the data-scarce network) and a cluster of networks with time series of phase current data (data-rich networks). Then, CCRE performs a range estimation of the imbalance-induced energy loss for the cluster of data-rich networks that resemble the data-scarce network. Chebyshev's inequality is applied to narrow down this range, which represents the confidence interval of the imbalance-induced energy loss for the data-scarce network. Case studies reveal that, given such a few data from the data-scarce networks, more than 80% of these networks are classified to the correct clusters and the confidence of the imbalance-induced energy loss estimation is 89%.
               