Laboratory testing was conducted to evaluate strain concentrations adjacent to high-density polyethylene (HDPE) geomembrane seams loaded in tension perpendicular to the seam. Strain concentrations were evaluated using digital image correlation… Click to show full abstract
Laboratory testing was conducted to evaluate strain concentrations adjacent to high-density polyethylene (HDPE) geomembrane seams loaded in tension perpendicular to the seam. Strain concentrations were evaluated using digital image correlation (DIC) on specimens meeting the ASTM criteria for wide-width tensile testing. The tensile strain in the zone of strain concentration adjacent to the seam from the DIC analysis was compared to the strain predicted using theoretical seam strain concentration factors. While the average strain in the zone of strain concentration was relatively close to the theoretical value, the maximum tensile strain in this zone was significantly greater than the value predicted using the theoretical strain concentration factors. For average (global) tensile strains in the order of 3%, maximum strains measured by DIC in the zone of strain concentration were in the order of 9 to 11%, compared to values on the order of 5 to 6% predicted using the theoretical strain concentration factors....
               