The current standard of residential buildings is based on well-insulated and airtight construction as an effective way to reduce primary energy consumption. On the other hand, this intensifies the issue… Click to show full abstract
The current standard of residential buildings is based on well-insulated and airtight construction as an effective way to reduce primary energy consumption. On the other hand, this intensifies the issue of the indoor air quality. In this paper, the applicability of a hybrid dehumidification/evaporative cooling system for the processing and supply of fresh air is evaluated. The proposed novel system employs cross-flow hollow-fiber membrane modules. To provide a better insight into this novel approach, the system’s performance is numerically investigated using a validated mathematical model. The proposed fresh air processing system provides supply air parameters in or close to the summer comfort range. The analyzed system is characterized by a high coefficient of performance (COP) of up to 33.2 at an outdoor air temperature in the range of 30 °C to 38 °C and a humidity ratio in the range of 8 g/kg to 14 g/kg. Moreover, a temperature difference of up to 9.7 °C can be obtained after the two-stage membrane processing and the mixing process.
               