LAUSR.org creates dashboard-style pages of related content for over 1.5 million academic articles. Sign Up to like articles & get recommendations!

DATA CENTER ENERGY CONSERVATION BY HEAT PIPE BASED PRE-COOLER SYSTEM

Photo from wikipedia

In the present paper, data center energy conservation systems based on the heat pipe heat exchanger (HPHE) pre-cooler to downsize the chiller capacity and working time has analysed, designed and… Click to show full abstract

In the present paper, data center energy conservation systems based on the heat pipe heat exchanger (HPHE) pre-cooler to downsize the chiller capacity and working time has analysed, designed and discussed. The proposed system utilizes thermal diode character of heat pipe to transfer waste heat from source (pre-cooler coolant) to ambient and have been analyzed as per metrological conditions in New York. HPHE Pre cooler with 118 heat pipes and designed for 30 °C ambient temperature has been designed to effectively dissipate 30 kW or more datacenter heat throughout the year. The payback period of the HPHE Pre cooler is around 2.8 years. Proposed heat pipe based system utilize natural ambient cold energy and thus does not have running cost and related greenhouse gas emissions.

Keywords: heat; pre cooler; heat pipe; energy

Journal Title: Frontiers in Heat and Mass Transfer
Year Published: 2019

Link to full text (if available)


Share on Social Media:                               Sign Up to like & get
recommendations!

Related content

More Information              News              Social Media              Video              Recommended



                Click one of the above tabs to view related content.